S11、S13 oil-immersed transformer
Category:
Keywords: Electrical Equipment
- Description
S11、S13 oil-immersed transformer
-
- Commodity name: S11、S13 oil-immersed transformer
Suitable for use in AC power systems with a frequency of 50Hz and a rated operating voltage of 10kV or below, serving as a distribution transformer for enterprises in petroleum, metallurgy, chemical, textile, light industry, etc., and locations with high levels of dust.
Overview
Suitable for use in AC power systems with a frequency of 50Hz and a rated operating voltage of 10kV or below, serving as a distribution transformer for enterprises in petroleum, metallurgy, chemical, textile, light industry, etc., and locations with high levels of dust.
Model Designation Meaning

Operating Conditions
◆ Installation Altitude: Not exceeding 1000m above sea level;
◆ Ambient Temperature: -40℃ to +40℃Structural Features
◆ Core
◇ The core is made of high-permeability grain-oriented cold-rolled silicon steel sheets. It features a modern design: fully step-lap jointed, laminated core. The core limbs have a multi-step circular cross-section, and the yokes have an equal cross-section to the core.
◆ Windings
◇ The windings employ corrugated oil ducts, utilize a non-varnish impregnation process, and are bound with tension tapes. All windings are concentric coils. The high-voltage winding has taps corresponding to the required tapping voltages, led out to the tap-changer mounted on the tank cover. The tap position must be changed only after the power supply is disconnected.
◆ Safety Protection Devices
◇ Transformers from 30 to 2000 kVA are equipped with pressure relief devices;
◇ Gas relays with alarm and trip contacts can be installed upon customer request;
◆ Oil Temperature Measurement Devices
◇ All transformers are provided with pockets for liquid-in-glass thermometers, located on the top of the tank and extending 120±10mm into the oil;
◇ Transformers from 1000 to 2000 kVA are equipped with outdoor-type signal thermometers;
◆ Transformer Tank
◇ The transformer tank is constructed with corrugated walls. The surface is treated with dust-resistant spray painting, resulting in a robust paint film.
◇ The corrugated panels not only provide cooling but also function as a "breathing" system. The elasticity of the corrugated panels compensates for the volume changes of the transformer oil caused by temperature fluctuations. Therefore, the fully sealed transformer does not require a conservator (oil expansion tank), reducing the overall height of the transformer.
◇ During sealing, the transformer undergoes vacuum oil filling, completely removing moisture from the transformer. The transformer oil is sealed and does not contact air. This effectively prevents the ingress of oxygen and moisture, which could degrade the transformer's insulation performance and accelerate oil aging. Consequently, regular oil sampling tests are not required.S11-M Type 6~10kV Oil-Immersed Distribution Transformer
Rated Capacity
(KVA)Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss
(W)Load Loss
(W)No-Load Current
(%)Short-Circuit Impedance
(%)HV (kV)
HV Tapping Range (%)
LV (kV)
30
11
10.5
10
6.3
6±5
±2×2.5%0.4
0.69Yyn0
Dyn11100
630/600
2.3
4
50
130
910/870
2.0
4
63
150
1090/1040
1.9
4
80
180
1310/1250
1.9
4
100
200
1580/1500
1.8
4
125
240
1890/1800
1.7
4
160
280
2310/2200
1.6
4
200
340
2730/2600
1.5
4
250
400
3200/3050
1.4
4
315
480
3830/3650
1.4
4
400
570
4520/4300
1.3
4
500
680
5410/5150
1.2
4
630
810
6200
1.1
4.5
800
960
7500
1.0
4.5
1000
1150
10300
1.0
4.5
1250
1360
12000
0.9
4.5
1600
1640
14500
0.8
4.5
2000
1960
19800
0.8
5
2500
2310
23000
0.7
5
S11-M Type 20kV Oil-Immersed Distribution Transformer
Rated Capacity
( KVA)Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss
( W)Load Loss
(W )No-Load Current
(%)Short-Circuit Impedance
(%)HV (kV)
HV Tapping Range (%)
LV (kV)
50
20
22
24±5%
±2×2.5%0.4
Dyn11
Yyn0210
1270/1210
2.00
6.5
100
290
2120/2020
1.80
6.5
125
340
2500/2380
1.70
6.5
160
360
2970/2830
1.60
6.5
200
430
3500/3330
1.50
6.5
250
510
4160/3960
1.40
6.5
315
610
5010/4770
1.40
6.5
400
730
6050/5760
1.30
6.5
500
860
7280/6930
1.20
6.5
630
1040
8280
1.10
6.5
800
1230
9900
1.00
6.5
1000
1440
12150
1.00
6.5
1250
1760
14670
0.90
6.5
1600
2120
17550
0.80
6.5
Note: For transformers with a rated capacity of 500kVA and below, The load loss value above the slash ( / ) in the table applies to connection symbols Dyn11 or Yzn11. The load loss value below the slash ( / ) applies to connection symbol Yyn0.
S13-M Type 6~10kV Oil-Immersed Distribution Transformer
Rated Capacity
(KVA)Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss
( W)Load Loss
(W )No-Load Current
(%)Short-Circuit Impedance
(%)HV (kV)
HV Tapping Range (%)
LV (kV)
30
6
6.3
6.6
10
10.5
11±5
±2×2.5%0.4
Dyn11
Yzn11
Yyn080
630/600
1.8
4
50
100
910/870
1.6
4
63
110
1090/1040
1.6
4
80
130
1310/1250
1.5
4
100
150
1580/1500
1.4
4
125
170
1890/1800
1.4
4
160
200
2310/2200
1.3
4
200
240
2730/2600
1.2
4
250
290
3200/3050
1.2
4
315
340
3830/3650
1.1
4
400
410
4520/4300
1.1
4
500
480
5410/5150
1.0
4
630
570
6200
0.9
4.5
800
Dyn11
Yyn0700
7500
0.8
4.5
1000
830
10300
0.8
4.5
1250
970
12000
0.7
4.5
1600
1170
14500
0.6
4.5
S13-M Type 20kV Oil-Immersed Distribution Transformer
Rated Capacity
(KVA)Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss
( W)Load Loss
(W )No-Load Current
(%)Short-Circuit Impedance
(%)HV (kV)
HV Tapping Range (%)
LV (kV)
50
20
22
24±5
±2×2.5%0.4
Dyn11
Yyn0170
1270/1210
2.00
6.5
100
230
2120/2020
1.80
6.5
125
270
2500/2380
1.70
6.5
160
290
2970/2830
1.60
6.5
200
340
3500/3330
1.50
6.5
250
410
4160/3960
1.40
6.5
315
490
5010/4770
1.40
6.5
400
580
6050/5760
1.30
6.5
500
690
7280/6930
1.20
6.5
630
830
8280
1.10
6.5
800
980
9900
1.00
6.5
1000
1150
12150
1.00
6.5
1250
1410
14670
0.90
6.5
1600
1700
17550
0.80
6.5
Note:
1、For the load loss values in the table: The value above the slash ( / ) applies to the Dyn11 connection symbol. The value below the slash ( / ) applies to the Yyn0 connection symbol.
2、Performance parameters for capacities not listed shall be mutually agreed between the user and manufacturer.
Related Products
Get a Free Quote
Fill in your phone number and E-mail information, and we will contact you within one working day to solve your problems as soon as possible.
Henan Jinyu Electric Co., Ltd.
Service Hotline:400-688-0375
Tel:+86-18103909516
Email:hnjydq1999@126.com
Address: South Section of Chuangye Road, Ji County Industrial Cluster, Henan Province, Central Plains Electric City
Scan