S13 High overload distribution transformer

High overload capacity distribution transformers avoid the problem of serious short-term overload caused by population flow in rural areas, reduce grid operation costs, improve grid operation safety, and are a major direction for the selection of rural distribution transformers in the future.

whatsapp:

    S13 High overload distribution transformer

    • Description
    • Commodity name: S13 High overload distribution transformer

    High overload capacity distribution transformers avoid the problem of serious short-term overload caused by population flow in rural areas, reduce grid operation costs, improve grid operation safety, and are a major direction for the selection of rural distribution transformers in the future.

    Overview

    In recent years, with the continuous increase of the floating population, the problem of serious overload operation of distribution transformers in rural areas during the high temperature season and the Spring Festival has emerged. To solve this problem, our company has responded to the call of the State Grid Corporation in recent years to actively carry out the research and application of high overload capacity distribution transformers. High overload distribution transformers have been developed. 
    According to the typical load characteristics of the comprehensive rural power grid substations, the high overload performance of the high overload capacity distribution transformer will meet the design requirements of 1.5 times the rated capacity for 6 hours, 1.75 times the rated capacity for 3 hours, and 2.0 times the rated capacity for 1 hour of phased continuous operation, without affecting the normal service life of the transformer. The high overload capacity distribution transformer avoids the problem of short-term serious overload caused by population flow in rural areas, reduces the cost of grid operation, improves grid operation safety, and is a major direction for the future selection of rural distribution transformers.

    Model Meaning

    The composition and numbering method of the product model of the high overload capacity distribution transformer (hereinafter referred to as "high overload distribution") are as follows, according to JB/T 3837:

    Example: A three-phase, oil-immersed, self-cooled, double-winding, no-excitation voltage regulation, insulation heat resistance grade F, loss level code "11", rated capacity of 100KVA kV voltage level sealed 
    The model of the high overload distribution is: S11-M(F)-100/10GZ.

    Product Features

    ◆ The product has high efficiency, low loss, and low noise characteristics; 
    ◆ Good internal heat dissipation, strong short-circuit capacity, and high safety performance; 
    ◆ Low no-load and load losses; 
    ◆ Reliable operation, long life, and maintenance-free.

    S11-M type 6~10kV

    Rated 
    Capacity(KVA)

    Voltage Combination and Tap Range

    Connection 
    Group Number

    No-load Loss 
    (kW)

    Load Loss 
    (kW)

    No-load Current(%)

    Impedance Voltage 
    (%)

    High Voltage(kV)

    High Voltage Tap Range%

    Low Voltage(kV)

    50

    10
    10.5
    11

    ±5% 
    ±2×2.5%

    0.4

    Yyn0
    Dyn11

    130

    910/870

    1.1

    4

    100

    200

    1580/1500

    1

    4

    200

    340

    2730/2600

    0.9

    4

    S13-M type 6~10kV

    Rated 
    Capacity(KVA)

    Voltage Combination and Tap Range

    Connection 
    Group Number

    No-load Loss 
    (kW)

    Load Loss 
    (kW)

    No-load Current(%)

    Impedance Voltage 
    (%)

    High Voltage(kV)

    High Voltage Tap Range%

    Low Voltage(kV)

    50

    10
    10.5
    11

    ±5% 
    ±2×2.5%

    0.4

    Yyn0
    Dyn11

    100

    910/870

    0.8

    4

    100

    150

    1580/1500

    0.7

    4

    200

    240

    2730/2600

    0.6

    4

    Note: 
    1. According to the requirements, the high voltage tap range of the transformer can be ±2×2.5%. 
    2. Other capacity product performance parameters shall be determined through consultation between the user and the manufacturer.

Related Products

SRM16-12/24 Fully insulated inflatable cabinet

SRM16-12/24 fully insulated and gas-filled switchgear is widely used in 10kV/20kV power distribution systems and is the preferred switch product for substations and distribution systems of various users in urban and rural areas.

SCB10、SCB11 Epoxy resin cast dry-type transformer

This product has a wide range of applications, and is especially suitable for use in places with high fire safety requirements, such as mines, oil fields, subways, power plants, schools, hospitals, commercial centers, high-rise buildings, and all indoor configuration systems.

XGN-12 Solid insulated ring network cabinet

The XGN-12 solid insulation ring network cabinet switchgear is a new generation of environmentally friendly solid insulation ring network cabinets independently developed by our company.

S13 High overload distribution transformer

High overload capacity distribution transformers avoid the problem of serious short-term overload caused by population flow in rural areas, reduce grid operation costs, improve grid operation safety, and are a major direction for the selection of rural distribution transformers in the future.