KYN61-40.5 Armoured metal enclosed switchgear
Category:
Keywords: Electrical Equipment
- Description
KYN61-40.5 Armoured metal enclosed switchgear
-
- Commodity name: KYN61-40.5 Armoured metal enclosed switchgear
The KYN61-40.5 armored metal-enclosed switchgear (hereinafter referred to as the switchgear cabinet) is a switchgear unit designed and improved by our factory based on our previous products.
Overview
The KYN61-40.5 armored metal-enclosed switchgear (hereinafter referred to as the switchgear cabinet) is a redesigned and upgraded version of our factory’s previous product. It is suitable for three-phase AC power systems with a frequency of 50 Hz and is used for receiving and distributing electrical energy, as well as for controlling, protecting, and monitoring the circuit.
This switchgear cabinet is equipped with a variety of interlocks to prevent misoperation, including interlocks that prevent the handcart from being moved under load, prevent the earthing switch from being closed while energized, and prevent unauthorized entry into energized compartments.
This switchgear is equipped with high-performance ZN85 and VN1 vacuum circuit breakers, or ABB’s VD4 and HD4 series vacuum circuit breakers. The switchgear is a distribution device that features advanced technology, stable performance, a rational structure, convenient operation, and high safety and reliability.Model Meaning

Key Features
◆ The cabinet body is fabricated from aluminum-zinc coated steel sheets using CNC machining and then assembled by bolting or riveting, resulting in a fully modular structure.
◆ It can be equipped simultaneously with ZN85-40.5 vacuum circuit breaker hand carts, VN1, VD4, or HD4 vacuum circuit breaker hand carts, and the main busbar of the switchgear can be directly connected without the need for a transition cabinet.◆ The cable compartment offers ample space, ensuring that the clear air clearance between phases exceeds 300 mm, eliminating the need for additional insulating partitions between phases.
Referenced Standards
This switchgear is designed and manufactured in accordance with the following standards:
GB 11022 Common Technical Requirements for High-Voltage Switchgear and Control Equipment;
GB 3906: 3–40.5 kV AC metal-enclosed switchgear and control equipment;
GB 1984 AC High-Voltage Circuit Breakers;
DL/T 404 Technical Specifications for Ordering Indoor AC High-Voltage Switchgear;
IEC 60694:2002 Common technical requirements for high-voltage switchgear and controlgear; IEC 62271-200: AC metal-enclosed switchgear and controlgear with rated voltages above 1 kV and up to and including 52 kV; IEC 62271-100:2003 High-voltage switchgear and controlgear—Part 100: High-voltage AC circuit breakers.Terms of Use
◆ Ambient temperature: not higher than +40°C, not lower than -25°C;
◆ Altitude: not exceeding 1000 m;
◆ Relative humidity: daily average not greater than 95%; monthly average not greater than 90%.
◆ Locations free from flammable gases, explosion hazards, severe contamination, chemical corrosion, and frequent severe vibrations.Environmental conditions
When the switchgear is operated under ambient conditions that exceed those specified in this user manual, the manufacturer and the user may negotiate and reach an agreement on any special operating conditions that go beyond the normal operating limits. To prevent condensation, the switchgear is equipped with a heater, which shall be put into service when the switchgear is in standby mode. Even during normal operation, attention should be paid to ensuring that the heater is properly activated.
The heat dissipation issue in switchgear cabinets can be addressed by installing additional ventilation equipment.Technical Specifications
Main Technical Parameters of Switchgear Project Unit Parameters Rated voltage kilovolt 40.5 Rated Insulation Level 1 min power-frequency withstand voltage kilovolt 95 (isolation break 115) Lightning Impulse Withstand Voltage (Peak) kilovolt 185 (Isolation Break 115) Rated frequency Hertz 50 Rated current of the main busbar A 630 ~ 2500 Rated short-circuit breaking current kA 31.5 Rated short-time withstand current (4 s) kA 25 Rated Peak Withstand Current kA 31.5 Rated Voltage of the Auxiliary Control Circuit V 25 ※ Forced Air Cooling
Technical Parameters of the ZN85-40.5 Vacuum Circuit Breaker Project Unit Parameters Rated voltage kilovolt 40.5 Rated Insulation Level 1 min power-frequency withstand voltage kilovolt 95 (isolation break 115) Lightning Impulse Withstand Voltage (Peak) kilovolt 185 (Isolation Break 115) Rated frequency Hertz 50 Rated current A 630, 1000, 1250, 1600; 1250, 1600, 2000, 2500, 3150※ Rated short-circuit breaking current kA 25; 31.5 Rated short-time withstand current (4 s) kA 25; 31.5 Rated Peak Withstand Current kA 63; 80 Rated Operating Sequence - Open (O)-0.3s - Close (CO)-180s - Close (CO) Rated short-circuit breaking current breaking operations next 20 Rated cable charging and breaking current A 25 Rated breaking current of capacitor bank A 400 Capacitive Current Switching Performance Level C2 Closing time milliseconds 40~100 Trip time milliseconds 30~60 Mechanical life next 10000 ※ Forced Air Cooling
Technical Parameters of the VD4 Series Vacuum Circuit Breaker Project Unit Parameters Rated voltage kilovolt 40.5 Rated Insulation Level 1 min power-frequency withstand voltage kilovolt 95 (isolation break 115) Lightning Impulse Withstand Voltage (Peak) kilovolt 185 (Isolation Break 115) Rated frequency Hertz 50 Rated current A 1250, 1600, 2000, 2500, 3150※ Rated short-circuit breaking current kA 31.5 ※ Forced Air Cooling
Technical Parameters of the VD4 Series Vacuum Circuit Breaker Project Unit Parameters Rated short-time withstand current (4 s) kA 31.5 Rated Peak Withstand Current kA 80 Rated Operating Sequence - Open (O) - 0.3 s - Close-Open (CO) - 180 s - Close-Open (CO) Closing time milliseconds 55~67 Trip time milliseconds 33~45 Arc duration milliseconds ≤15 Breaking time milliseconds 48~60 ※ Forced Air Cooling
Related Products
Get a Free Quote
Fill in your phone number and E-mail information, and we will contact you within one working day to solve your problems as soon as possible.
Henan Jinyu Electric Co., Ltd.
Service Hotline:400-688-0375
Tel:+86-18103909516
Email:hnjydq1999@126.com
Address: South Section of Chuangye Road, Ji County Industrial Cluster, Henan Province, Central Plains Electric City
Scan