S11 35kV oil-immersed transformer

The product features high efficiency, low loss, and low noise.

Keywords: Electrical Equipment

whatsapp:

    S11 35kV oil-immersed transformer

    • Description
    • Commodity name: S11 35kV oil-immersed transformer

    The product features high efficiency, low loss, and low noise.

    Overview

    ◆ High efficiency, low loss, and low noise; ◆ Good internal heat dissipation, strong short-circuit resistance, and high safety performance; ◆ Low no-load and load losses; ◆ Reliable operation, long life, and maintenance-free.

    50KVA~1600KVA Three-phase Double-winding Un-excited Voltage Regulation Distribution Transformer

    Rated Capacity 
    (KVA)

    Voltage Combination and Tap Range

    Connection Group Mark

    Losses (kW)

    No-load Current

    (%)

    Short-circuit Impedance

    (%)

    High Voltage 
    (kV)

    High Voltage Tap Range

    %

    Low Voltage 
    (kV)

     

    No-load

    Load

    50

    35

    ±5

    0.4

    Dyn11
    Yyn0

    0.19

    1.21/1.15

    2.00

    6.5

    100

    0.26

    2.01/1.92

    1.80

    125

    0.31

    2.38/2.26

    1.70

    160

    0.32

    2.82/2.69

    1.60

    200

    0.39

    3.33/3.16

    1.50

    250

    0.46

    3.95/3.76

    1.40

    315

    0.55

    4.76/4.53

    1.40

    400

    0.66

    5.75/5.47

    1.30

    500

    0.77

    6.92/6.58

    1.20

    630

    0.94

    7.87

    1.10

    800

    1.11

    9.41

    1.00

    1000

    1.30

    11.54

    1.00

    1250

    1.58

    13.94

    0.90

    1600

    1.91

    16.67

    0.80

    Note 1: For transformers with a rated capacity of 500KVA or less, the load loss values above the slash in the table apply to the Dyn11 connection group, and the load loss values below the slash apply to the Yyn0 connection group. 
    Note 2: Transformers with a high-voltage tap range of ±2×2.5% can be provided according to user needs. Note 3: Dimensions are designed according to specific user requirements.

    630KVA~31500KVA Three-phase Double-winding Un-excited Voltage Regulation Power Transformer

    Rated Capacity 
    (KVA)

    Voltage Combination and Tap Range

    Connection Group 
    Mark

    Losses (kW)

    No-load 
    Current (%)

    Short Circuit 
    Impedance (%)

    High Voltage 
    (kV)

    High Voltage Tap 
    Range %

    Low Voltage 
    (kV)

    No-load

    Load

    630

    35

    ±5

    3.15
    6.3
    10.5

    Yd11

    0.94

    7.87

    1.10

    6.5

    800

    1.11

    9.41

    1.00

    1000

    1.30

    11.54

    1.00

    1250

    1.58

    13.94

    0.90

    1600

    1.91

    16.67

    0.80

    2000

    2.45

    18.38

    0.70

    2500

    2.88

    19.67

    0.60

    3150

    35~38.5

    ±5

    3.15
    6.3
    10.5

    3.42

    23.09

    0.56

    7.0

    4000

    4.07

    27.36

    0.56

    5000

    4.86

    31.38

    0.48

    6300

    5.90

    35.06

    0.48

    7.5

    8000

    35~38.5

    ±2×2.5

    3.15
    3.3
    6.3
    6.6
    1.05
    11

    Yd11

    8.10

    38.48

    0.42

    10000

    9.79

    45.32

    0.42

    12500

    11.34

    53.87

    0.40

    8.0

    16000

    13.68

    65.84

    0.40

    20000

    16.20

    79.52

    0.40

    25000

    19.15

    94.05

    0.32

    31500

    22.75

    112.86

    0.32

    Note 1: Dimensions are designed according to specific user requirements.

    2000KVA~20000KVA Three-phase Double-winding On-load Tap-changing Power Transformer

    Rated Capacity 
    (KVA)

    Voltage Combination and Tap Range

    Connection Group 
    Mark

    Losses (kW)

    No-load 
    Current (%)

    Short Circuit 
    Impedance (%)

    High Voltage 
    (kV)

    High Voltage Tap 
    Range %

    Low Voltage 
    (kV)

    No-load

    Load

    2000

    35

    ±3×2.5

    6.3
    10.5

    Yd11

    2.59

    19.24

    0.80

    6.5

    2500

    3.06

    20.64

    0.80

    3150

    35~38.5

    ±3×2.5

    6.3
    10.5

    3.64

    24.71

    0.72

    7.0

    4000

    4.36

    29.16

    0.72

    5000

    5.22

    34.20

    0.68

    6300

    6.34

    36.77

    0.68

    7.5

    8000

    8.86

    40.61

    0.60

    10000

    35~38.5

    ±3×2.5

    6.3
    6.6
    10.5
    11

    Ynd11

    10.44

    48.05

    0.60

    8.0

    12500

    12.31

    56.86

    0.56

    16000

    14.81

    70.32

    0.54

    20000

    17.51

    82.78

    0.54

    Note 1: Dimensions are designed according to specific user requirements.

    50KVA~1600KVA Three-phase Double-winding Un-excited Voltage Regulation Distribution Transformer

    Rated Capacity 
    (KVA)

    Voltage Combination and Tap Range

    Connection Group 
    Mark

    Losses (kW)

    No-load 
    Current (%)

    Short Circuit 
    Impedance (%)

    High Voltage 
    (kV)

    High Voltage Tap 
    Range %

    Low Voltage 
    (kV)

    No-load

    Load

    50

    35

    ±5

    0.4

    Dyn11
    Yyn0

    0.17

    1.21/1.15

    2.00

    6.5

    100

    0.23

    2.01/1.92

    1.80

    125

    0.27

    2.38/2.26

    1.70

    160

    0.29

    2.82/2.69

    1.60

    200

    0.34

    3.33/3.16

    1.50

    250

    0.41

    3.95/3.76

    1.40

    315

    0.49

    4.76/4.53

    1.40

    400

    0.58

    5.75/5.47

    1.30

    500

    0.69

    6.92/6.58

    1.20

    630

    0.83

    7.87

    1.10

    800

    0.98

    9.41

    1.00

    1000

    1.15

    11.54

    1.00

    1250

    1.41

    13.94

    0.90

    1600

    1.70

    16.67

    0.80

    Note 1: For transformers with a rated capacity of 500KVA or less, the load loss values above the slash in the table apply to the Dyn11 connection group, and the load loss values below the slash apply to the Yyn0 connection group. 
    Note 2: Transformers with a high-voltage tap range of ±2×2.5% can be provided according to user needs.

    630KVA~31500KVA Three-phase Double-winding Un-excited Voltage Regulation Power Transformer

    Rated Capacity 
    (KVA)

    Voltage Combination and Tap Range

    Connection Group 
    Mark

    Losses 
    (kW)

    No-load 
    Current (%)

    Short Circuit 
    Impedance (%)

    High Voltage 
    (kV)

    High Voltage Tap 
    Range %

    Low Voltage 
    (kV)

    No-load

    Load

    630

    35

    ±5

    3.15
    6.3
    10.5

    Yd11

    0.83

    7.87

    1.10

    6.5

    800

    0.98

    9.41

    1.00

    1000

    1.15

    11.54

    1.00

    1250

    1.41

    13.94

    0.90

    1600

    1.70

    16.67

    0.80

    2000

    2.18

    18.38

    0.70

    2500

    2.56

    19.67

    0.60

    3150

    35~38.5

    ±5

    3.15
    6.3
    10.5

    3.04

    23.09

    0.56

    7.0

    4000

    3.62

    27.36

    0.56

    5000

    4.32

    31.38

    0.48

    6300

    5.25

    35.06

    0.48

    7.5

    8000

    35~38.5

    ±2×2.5

    3.15
    3.3
    6.3
    6.6
    1.05
    11

    Yd11

    7.20

    38.48

    0.42

    10000

    8.70

    45.32

    0.42

    12500

    10.08

    53.87

    0.40

    8.0

    16000

    12.16

    65.84

    0.40

    20000

    14.40

    79.52

    0.40

    25000

    17.02

    94.05

    0.32

    31500

    20.22

    112.86

    0.32

    Note 1: Dimensions are designed according to specific user requirements.

    2000KVA~20000KVA Three-phase Double-winding On-load Tap-changing Power Transformer

    Rated Capacity 
    (KVA)

    Voltage Combination and Tap Range

    Connection Group 
    Mark

    Losses 
    (kW)

    No-load 
    Current (%)

    Short Circuit 
    Impedance (%)

    High Voltage 
    (kV)

    High Voltage Tap 
    Range %

    Low Voltage 
    (kV)

    No-load

    Load

    2000

    35

    ±3×2.5

    6.3
    10.5

    Yd11

    2.30

    19.24

    0.80

    6.5

    2500

    2.72

    20.64

    0.80

    3150

    35~38.5

    ±3×2.5

    6.3
    10.5

    3.23

    24.71

    0.72

    7.0

    4000

    3.87

    29.16

    0.72

    5000

    4.64

    34.20

    0.68

    6300

    5.63

    36.77

    0.68

    7.5

    8000

    7.87

    40.61

    0.60

    10000

    35~38.5

    ±3×2.5

    6.3
    6.6
    10.5
    11

    Ynd11

    9.28

    48.05

    0.60

    8.0

    12500

    10.94

    56.86

    0.56

    16000

    13.17

    70.32

    0.54

    20000

    15.57

    82.78

    0.54

Related Products

SRM16-12/24 Fully insulated inflatable cabinet

SRM16-12/24 fully insulated and gas-filled switchgear is widely used in 10kV/20kV power distribution systems and is the preferred switch product for substations and distribution systems of various users in urban and rural areas.

SCB10、SCB11 Epoxy resin cast dry-type transformer

This product has a wide range of applications, and is especially suitable for use in places with high fire safety requirements, such as mines, oil fields, subways, power plants, schools, hospitals, commercial centers, high-rise buildings, and all indoor configuration systems.

XGN-12 Solid insulated ring network cabinet

The XGN-12 solid insulation ring network cabinet switchgear is a new generation of environmentally friendly solid insulation ring network cabinets independently developed by our company.

S13 High overload distribution transformer

High overload capacity distribution transformers avoid the problem of serious short-term overload caused by population flow in rural areas, reduce grid operation costs, improve grid operation safety, and are a major direction for the selection of rural distribution transformers in the future.