KBSG Mine Explosion-proof Dry-type Transformer

The KBSG mine-use flameproof dry-type transformer complies with the requirements of GB 8286-2005, “Flameproof Mobile Substations for Mining.” The insulating materials exhibit excellent thermal stability.

Keywords: Electrical Equipment

whatsapp:

    KBSG Mine Explosion-proof Dry-type Transformer

    • Description
    • Commodity name: KBSG Mine Explosion-proof Dry-type Transformer

    The KBSG mine-use flameproof dry-type transformer complies with the requirements of GB 8286-2005, “Flameproof Mobile Substations for Mining.” The insulating materials exhibit excellent thermal stability.

    Overview

    The KBSG explosion-proof dry-type transformer for mining applications complies with the requirements of GB 8286-2005, “Explosion-Proof Mobile Substation for Mining.” It features excellent thermal stability of insulation materials, employing Class H or Class C insulation. The cooling method is ANAN, making it suitable for mine shafts, mines, tunnels, and other environments where methane–air mixtures and coal dust are present and there is a risk of explosion. It is also appropriate for environments containing gases and vapors that do not corrode metals or degrade insulation. Operated at a rated frequency of 50 Hz, with a primary-side voltage of 6 kV or 10 kV, in an ungrounded neutral three-phase power system, it provides power to various power-driven equipment and electrical loads in the operating environment.

    Model and Meaning

    Main Technical Parameters of 6 kV Class KBSG Explosion-Proof Dry-Type Transformer for Mining

    Rated Capacity (kVA)Voltage Combination (kV)Connection Group DesignationNo-load loss (kW)Load Loss (kW)No-load current (%)Impedance Voltage (%)External dimensions (length × width × height) (mm)Weight (kg)Track gauge (mm)
    50High pressure 
    (6+5%) 
    0.693/0.4 
    1.2/0.693 
    1.2
    3.45
     
    Yy0 (d11)3505502.542225×950×11601350

    600

    900

    1005209202.542500×950×14301600
    2008201550242640×950×14452050
    2509501800242750×965×15302300
    315110021501.842830×975×15402500
    400130026001.842830×995×15502650
    500150031001.542850×1050×15703100
    630180036801.543020×1080×14504310
    80020504500143020×1080×15104650
    1000Yy0 (d11) 
    Dyn11
    23505400143030×1130×15405150
    125027506500143120×1160×16105900
    1600335080000.843120×1200×17507250
    2000380095000.64.53225×1220×179010820
    25004500106000.653580×1230×185013850
    31505300125000.65.53820×1260×189018250
    40006100140000.663930×1400×192020810

    Main Technical Parameters of 10 kV Class KBSG Explosion-Proof Dry-Type Transformer for Mining

    Rated Capacity (kVA)Voltage Combination (kV)Connection Group DesignationNo-load loss (kW)Load Loss (kW)No-load current (%)Impedance Voltage (%)External dimensions (length × width × height) (mm)Weight (kg)Track gauge (mm)
    50

    High pressure

    (10±5%)

    0.693/0.4

    1.2/0.693

    1.2

    3.45

    Yy0

    (d11)

    39006802.542310×950×12951400

    600

    900

    10056010502.542430×950×14301800
    2009501800242730×950×15252200
    25011002100242760×950×15402500
    315130025001.842800×980×15552800
    400150030001.842950×1050×16103000
    500175035001.542950×1050×16103300
    630200041001.543200×1080×14504400
    800

    Yy0

    (d11)

    Dyn11

    230051001.243200×1080×16004700
    1000260061001.243200×1110×16755900
    12503100740014.53250×1125×17406500
    16003800850014.53450×1245×18308300
    2000450097000.753665×1250×190010900
    25005200108000.75.53780×1390×190013930
    31506100128000.75.53880×1390×190018350
    40007000150000.764210×1450×190020910

Related Products

XGN-12 Solid insulated ring network cabinet

The XGN-12 solid insulation ring network cabinet switchgear is a new generation of environmentally friendly solid insulation ring network cabinets independently developed by our company.

S13 High overload distribution transformer

High overload capacity distribution transformers avoid the problem of serious short-term overload caused by population flow in rural areas, reduce grid operation costs, improve grid operation safety, and are a major direction for the selection of rural distribution transformers in the future.

SBH15-M Oil-Immersed Amorphous Alloy Distribution Transformer

Transformers can step down grid voltage to the levels required by the power system or load, thereby enabling the transmission and distribution of electrical energy. This transformer can replace conventional silicon-steel-laminated transformers and is widely used in outdoor distribution systems. Extensive deployment of this product in the power grid delivers significant energy-saving benefits and helps reduce atmospheric pollution.

SRM16-12/24 Fully insulated inflatable cabinet

SRM16-12/24 fully insulated and gas-filled switchgear is widely used in 10kV/20kV power distribution systems and is the preferred switch product for substations and distribution systems of various users in urban and rural areas.

SCB10 and SCB11 Epoxy-resin Cast Dry-type Transformers

This product has a wide range of applications and is particularly well suited for use in environments with stringent fire safety requirements, such as mines, oil fields, subways, power plants, schools, hospitals, commercial centers, high-rise buildings, and all indoor installation systems.

KYN61-40.5 Armoured metal enclosed switchgear

The KYN61-40.5 armored metal-enclosed switchgear (hereinafter referred to as the switchgear cabinet) is a switchgear unit designed and improved by our factory based on our previous products.

Get a Free Quote

Fill in your phone number and E-mail information, and we will contact you within one working day to solve your problems as soon as possible.

%E7%AC%AC%E4%B8%80%EF%BC%8C%E6%9C%80%EF%BC%8C%E4%BC%98%E7%A7%80%EF%BC%8C%E5%A2%9E%E5%BC%BA%EF%BC%8C%E4%B8%80%E6%B5%81%EF%BC%8C%E5%8D%93%E8%B6%8A%EF%BC%8C%E9%A2%86%E5%85%88%EF%BC%8C%E5%85%88%E8%BF%9B%EF%BC%8C%E5%BC%95%E9%A2%86

Sorry,当前栏目暂无内容!

您可以查看其他栏目或返回 首页

Sorry,The current column has no content!

You can view other columns or return Home